POWER DOWN THE WIRING CENTRE
NOTICE: The Wiring Centre has 230v mains running through it, make sure the Wiring Centre has been isolated and there is no power connected to it before removing the cover
REMOVE THE TEST SENSOR CABLE
Remove the Test Sensor wire from C1, C2 and wire up the full Sensor bus you'd like to test into C1, C2. See fig. 1

Fig. 1: Sensor Bus Wiring Diagram
POWER UP THE WIRING CENTRE
Reconnect power to the Wiring Centre and wait for the Contro Hub to power up
NOTICE: When you can see the clock interface please wait an extra 15 seconds for background processes to start up before attempting to use the Control Hub
ADD SENSORS
Omnie 'O' -> Cogs -> General Params -> System Set Up -> Wcentre Settings -> Add Sensor -> Manual Mode -> SELECT: Wcentre 1 -> PRESS: TICK -> Increase the number to the total number of sensors you have on the bus -> PRESS: TICK -> Assignment ->Repeat this next step for all the sensors on your bus.
TOP TIP: You should use the APPENDIX 1: Assignment Table. See Fig. 2. to make inputting sensors faster and easier

Fig. 2: Appendix Table
TOP TIP: You can download this table template from the bottom of this page
START SYSTEM
Once you have added the rooms for just this Wiring Centre you can start the system
Omnie 'O' -> Cogs -> General Params -> System Set Up -> System Start -> POP UP: Yes
TOP TIP: The Control Hub will now communicate with the Wiring Centre, the red LED will stop flashing and some green LED's along the A rail will turn on
CHECK TEMPERATURES
Omnie 'O' -> House with Magnifying GlassYou should have all your rooms for this Wiring Centre showing on the screen showing two temperatures each. See fig. 3. If there is a reading on the top right for each room box then the Sensor, Control Hub and Wiring Centre are working as expected.
NOTICE: This may take up to 2 minutes to update a temperature reading for the sensor as the system is just starting up. This depends on how much wire is running through the bus (longer bus lengths may require a little extra time but no more than 5 minutes)

Fig. 3: Home View
TROUBLESHOOT
If one, or all of the sensors do not show a temperature reading after a few minutes, you should test each of the sensors on this bus. To do this just replace the sensor you used in the test set up with each one from your sensor bus and repeat the process.
If all the temperatures are showing, move on to the next Wiring Centre and repeat the process.
NOTICE: The most likely cause of a room not showing a temperature on the Control Hub is due to a wiring issue, this could be: lose connections in the terminal blocks, joins in the bus cable, incorrect wiring, missing C2 (i f) links
STOP SYSTEM
Omnie 'O' -> Cogs -> General Params -> System Set Up -> System Stop -> POP UP: YesTOP TIP: Once the system is stopped the Wiring Centre red LED will be flashing 3 short flashes